云南省综合医院洁净手术室综合性能检测结果分析 [中文引用][英文引用]

Analysis of Comprehensive Performance of Clean Operating Rooms in some General Hospitals in Yunnan Province

作者(英文):DUAN Zhiquan1  HUANG Guofei2  OU Qiusheng2  DI Juan2  LI Xiaoli2  YANG Jianbin2  LI Yang2 
单位(英文): 
关键词(英文):general hospital  clean opevation room  comprehensive performance  analysis 
分类号:S884.1+1
出版年·卷·期(页码):2019·9·第4期(369-372)
DOI:
-----摘要:-------------------------------------------------------------------------------------------

目的 了解云南省综合医院洁净手术室的综合性能,为保障手术室洁净质量提供参考。方法 采用现场采样检测方法,对云南省22家医院共125间洁净手术室的尘埃粒子数、温度、相对湿度、静压差、截面风速、换气次数、噪声、照度、沉降菌进行静态检测。采用卡方检验,分别比较分析不同洁净等级、新改建和投入使用≥1年的手术室中各检测指标的合格率。结果 125间洁净手术室尘埃粒子数、温度、相对湿度、静压差、截面风速、换气次数、噪声、照度、沉降菌的合格率分别为92.00%91.20%86.40%83.20%92.59%90.82%86.40%89.60%96.00%级和级洁净手术室悬浮粒子合格率高于级洁净手术室(P<0.05),级洁净手术室噪声合格率高于级和级洁净手术室(P<0.05)。新建或改建手术室的悬浮粒子、温度、相对湿度、静压差、截面风速、换气次数、噪声、照度和沉降菌的合格率高于投入使用≥1 a的手术室(P<0.05)。结论 云南省新建或改建洁净手术室合格率较高,但投入使用≥1 a的手术室各项指标检测合格率不容乐观,需加强管理和维护。

-----英文摘要:---------------------------------------------------------------------------------------

Objectives To understand the comprehensive performance of the clean operating rooms in some general hospitals in Yunnan. Methods 125 clean operating rooms in 22 general hospitals were monitored by field sampling. The dust particles, temperature, humidity, the static pressure difference, air velocity, ventilation, noise, illumination and airborne microorganism were tested under static condition. Chi-square test was used to analyze the qualified rates of operating rooms with different cleanliness grades, new renovation and operation for more than 1 year. Results In 125 clean operating rooms, the qualified rates of dust particles, temperature, humidity, the static pressure difference, air velocity, ventilation, noise, illumination and airborne microorganism were 92.00%91.20%86.40%83.20%92.59%90.82%86.40%89.60%96.00%, respectively. The qualified rate of dust particles of level or level operating rooms was higher than that of leveloperating rooms (P<0.05). The qualified rate of the noise of leveloperating rooms was higher than that of level or level operating rooms (P<0.05). The qualification rates of comprehensive performance of newly built or rebuilt clean operating rooms were higher than the clean operating rooms which have been used for more than one year (P<0.05). Conclusions Compared with newly built or rebuilt clean operating rooms, the comprehensive performance of clean operating rooms which have been used for more than one year were not satisfying in some general hospitals in Yunnan. Regular maintenance and management should be strengthened.

-----参考文献:---------------------------------------------------------------------------------------

欢迎阅读《环境卫生学杂志》!您是该文第 154 位读者!

若需在您的论文中引用此文,请按以下格式着录参考文献:
中文着录格式: 段智泉1,,黄国斐2,,欧秋生2,,狄娟2,,李晓俐2,,杨建斌2,,栗旸2.云南省综合医院洁净手术室综合性能检测结果分析.环境卫生学杂志.2019;9(4):369-372.
英文着录格式: DUAN,Zhiquan1,,HUANG,Guofei2,,OU,Qiusheng2,,DI,Juan2,,LI,Xiaoli2,,YANG,Jianbin2,,LI,Yang2.Analysis of Comprehensive Performance of Clean Operating Rooms in some General Hospitals in Yunnan Province..2019;9(4):369-372.